EasyManua.ls Logo

Samsung DVM S ECO BIG Series - Page 51

Samsung DVM S ECO BIG Series
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
Samsung Electronics 4-9
Discharge mode of DC link voltage
FAN PBA
INVERTER PBA
• Evenwhentheoutdoorunitpowerisoff,itisdangerous
when you come in contact with inverter PCB since it is
charged with high DC voltage.
• Whenreplacing/repairingthePCB,cut-offthepowerand
wait until the DC voltage is discharged before replacing /
repairing them. (Wait for more than 15 minutes to allow it
to discharge naturally.)
• During"DischargemodeofDClinkvoltage",voltageof
INV will be displayed.
• Ifinvertererrorisoccurred(E464/364,E461/361,etc.),
please wait more than 15 minutes until self-discharging
after shutting off the power because it can not enter a
discharge mode.
How to initiate
Press the K2 tact switch 3 times.
Etc.
Discharge is complete, the power of the Inverter
PCB is being blocked, communication function is
blocked, E206 will occur.