EasyManua.ls Logo

Samsung MCU-S4NEK3N - Wiring; Electrical Connections and Protection

Samsung MCU-S4NEK3N
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Refrigerant piping
20
WiringWiring
Installing the circuit breaker and wires
Power supply MCCB ELB Power cable Earth cable Communication cable
Max : 242V
Min : 198V
x [A]
x [A], 30mmA
0.1 sec
0.0039inch
2
(2.5mm
2
)
0.0039inch
2
(2.5mm
2
)
0.0012~0.0023inch
2
(0.75~1.5mm
2
)
J x [A] ≥ 1.25 X 1.1 X ∑Ai
(x [A] : MCCB/ELB ampheres, ∑Ai : Sum of the rated current ampheres of indoors)
Installing the wire
X Supply the 220-240V/208-230V power to L1, L2 (L, N) of MCU separately
X Connect the communication cable from the outdoor unit to F1, F2 of MCU.
X Power Line and communication line must be connected as shown in drawing.
Case 1 Case 2
220-240V/208-230V / Single Phase
(Supply separately)
ELB
MCCB
Outdoor
Unit
Indoor
Unit
Indoor
Unit
MCU
ELB
MCCB
Outdoor
Unit
Indoor
Unit
Indoor
Unit
MCU
Indoor
Unit
220-240V/208-230V / Single Phase
(Supply separately)
MCU
Case 3
ELB
MCCB
Outdoor
Unit
Indoor
Unit
MCU
Indoor
Unit
Indoor
Unit
220-240V/208-230V / Single Phase
(Supply separately)
Indoor Unit
ki]_TW]`WZhTW\pttj|GrniluRmyUGGGYW YWYYTXXTYYGGG㝘㤸G_a\_a\`