E-30
Switch Setting and Testing Operation (Cont.)
Ampere Limit Setting & Changing Procedure
WARNING
Do not adjust the Ampere Limit Switch, if it’s not necessary: before modifying
it, evaluate the total number of electric and electronics loads consumption and
use Ampere limits switch just as emergency solution or in case the system is
anyway oversized compared to real thermal load needed
.
Ampere Limit Switch is initially set to the default value (table below).
Ampere Limit Switch is on the PCB of outdoor unit.
Contact the authorized service technician or dealer for setting and changing
the Ampere Limit Switch.
Before changing the Ampere Limit Switch, turn off the main power of the system.
K 1
K 2 K 3
DIS01
SW0
2 SW01
K 4
DIS02
The designs and shape are subject to
change according to the model.
Outdoor PCB Display
Ampere Switch Selection
MH040FX
A2B
MH18VF1X
MH19VF1X
MH050FX
A2B MH060FX
A3B
MH070FX
A4B
MH080FX
A4B
Switch 3 4
9.0A
(Default)
13.5A
(Default)
14.5A
(Default)
16.6A
(Default)
(OFF)
ON ON
8.5A
11.0A 13.0A 14.0A
(OFF)
ON OFF
8.0A 9.0A 10.0A 11.0A
(OFF)
OFF ON
7.0A 8.0A 8.0A 10.0A
(OFF)
OFF OFF
Switch
Indoor unit
address
View data display
COMPLETING THE INSTALLATION
It could take maximum 60 minutes to operate for the protection of the compressor
if the outdoor temperature is below -5°C.