Pipe Checking Operation (Auto Addressing Mode)
Automated checking of pipe connection (Auto addressing option)
Turn on the outdoor unit and wait for one minute.
During these 60 seconds, the left dispaly DIS01 will show sequentially
00-01-02-03-...15-00
.
E199 is showed on the display PCB of outdoor unit.
- It means you didnt do “Pipe check operation“
Push [K1] button on the display PCB of outdoor unit once,
then begins to start “Pipe check operation with displaying as below.

Button [Κ1] 1 times
Display
DIS 01 DIS 02
[DIS 01] is flickering on the setting time.
Time duration
Outdoor Temperature
C or more Less than0°C
(Cool mode)
5min ~ 10 min
(Heat mode)
20min ~ 50 min
Expected time of 4 indoor units installation.
[DIS02] shows the indoor unit under searching
It could take more time depending on the indoor and outdoor temperature.

After completeing pipe check operation, it shows “ on the display PCB.

The left display DIS01 will show sequentially the following message:
00 - Estabilished communication with indoor unit A”;
01 - Estabilished communication with indoor unit “B”;
02 - Estabilished communication with indoor unit “C”;
03 - Estabilished communication with indoor unit “D”;
00 - Estabilished communication with indoor unit A...
Function of Step 3
Mode Function
Auto Addressing Checking the connection & addressing
Manual Addressing Checking the connection only
If the auto addressing does not work according to the indoor unit capacity,
model or installation condition, apply the manual addressing.
When SW01 set "0" on Auto address mode, it means you install the maximum
number of indoor unit.
1) Installation ID Unit Number= MAX Installation ID Unit Number of OD Unit.
Don't need set SW01.
2) Installation ID Unit Number< MAX Installation ID Unit Number of OD Unit.
Pls set SW01 as the number of which you install the indoor unit.
On Manual address mode,you must set SW01 as the number of which you install
the indoor unit.
COMPLETING THE INSTALLATION
08'FJM_OUTDOOR_28896A_IM_E.indd 31 2007-12-12 14:28:56