E-9
ENGLISH
INSTALLING THE INDOOR UNIT
Cutting/Extending the Piping
1
Make sure that you have the required tools available (pipe cutter, reamer,
flaring tool and pipe holder).
2
If you wish to shorten the piping, cut it using a pipe cutter, taking care to
ensure that the cut edge remains at a 90° angle with the side of the pipe,
and referring to the illustrations below for examples of edges cut correctly
and incorrectly.
3
To prevent any gas from leaking out, remove all burrs at the cut end of the
pipe, using a reamer.
4
Slide a flare nut on to the pipe and modify the flare.
Outer Diameter(D) Depth(A)
6.35 mm 1.3 mm
9.52 mm 1.8 mm
12.70 mm 2.0 mm
5
Check that the flaring is correct, referring to the illustrations below for
examples of incorrect flaring.
Inclined Damaged Surface Cracked Uneven Thickness
6
Align the pipes to be connected and tighten the flare nuts first manually and
then with a torque wrench, applying the following torque.
Outer Diameter Torque(kgf•cm)
6.35 mm 140~170
9.52 mm 250~280
12.70 mm 380~420
7
For further details on how to connect up to the outdoor unit and purge the
circuit, refer to page 17.
xx x x
Oblique Rough Burr