291
6. Capacity Correction
Outdoor Units
AC052RXADKG/EU
Cooling
Pipe Length (m)
5 10 15 20 25 30
Level Difference (m)
30 - - - - - -
25 - - - - - -
20 - - - 0.92 0.90
15 - - 0.94 0.92 0.90
10 - 0.96 0.94 0.92 0.90
5 0.98 0.96 0.94 0.92 0.90
0 1 0.98 0.96 0.94 0.92 0.90
-5 0.97 0.95 0.93 0.91 0.89
-10 - 0.94 0.93 0.91 0.89
-15 - - 0.92 0.90 0.88
-20 - - - - 0.89 0.86
-25 - - - - - -
-30 - - - - -
Heating
Pipe Length (m)
5 10 15 20 25 30
Level Difference (m)
30 - - - - - -
25 - - - - - -
20 - - - - 0.94 0.92
15 - - - 0.95 0.94 0.92
10 - - 0.97 0.95 0.94 0.92
5 - 0.98 0.97 0.95 0.94 0.92
0 1 0.98 0.97 0.95 0.94 0.92
-5 - 0.98 0.97 0.95 0.94 0.92
-10 - - 0.97 0.95 0.94 0.92
-15 - - - 0.95 0.94 0.92
-20 - - - - 0.94 0.92
-25 - - - - - -
-30 - - - - - -