6. Capacity Correction
292
Outdoor Units
AC071/100/120RXAD*G/EU
Cooling
Pipe Length (m)
5 10 15 20 25 30 35 40 45 50
Level Difference (m)
30 - - - - - - 0.93 0.92 0.91 0.90
25 - - - - - 0.94 0.93 0.92 0.91 0.90
20 - - - - 0.96 0.94 0.93 0.92 0.91 0.90
15 - - - 0.97 0.96 0.94 0.93 0.92 0.91 0.90
10 - - 0.98 0.97 0.96 0.94 0.93 0.92 0.91 0.90
5 - 0.99 0.98 0.97 0.96 0.94 0.93 0.92 0.91 0.90
0 1 0.99 0.98 0.97 0.96 0.94 0.93 0.92 0.91 0.90
-5 - 0.98 0.97 0.96 0.95 0.94 0.93 0.92 0.91 0.89
-10 - - 0.97 0.96 0.95 0.94 92 0.91 0.90 0.88
-15 - - - 0.95 0.95 0.93 0.92 0.91 0.89 0.88
-20 - - - - 0.94 0.93 0.92 0.90 0.89 0.87
-25 - - - - - 0.92 0.91 0.90 0.88 0.86
-30 - - - - - - 0.91 0.89 0.88 0.85
Heating
Pipe Length (m)
5 10 15 20 25 30 35 40 45 50
Level Difference (m)
30 - - - - - - 0.95 0.94 0.93 0.92
25 - - - - - 0.96 0.95 0.94 0.93 0.92
20 - - - - 0.96 0.96 0.95 0.94 0.93 0.92
15 - - - 0.97 0.96 0.96 0.95 0.94 0.93 0.92
10 - - 0.98 0.97 0.96 0.96 0.95 0.94 0.93 0.92
5 - 0.99 0.98 0.97 0.96 0.96 0.95 0.94 0.93 0.92
0 1 0.99 0.98 0.97 0.96 0.96 0.95 0.94 0.93 0.92
-5 - 0.99 0.98 0.97 0.96 0.96 0.95 0.94 0.93 0.92
-10 - - 0.98 0.97 0.96 0.96 0.95 0.94 0.93 0.92
-15 - - - 0.97 0.96 0.96 0.95 0.94 0.93 0.92
-20 - - - - 0.96 0.96 0.95 0.94 0.93 0.92
-25 - - - - - 0.96 0.95 0.94 0.93 0.92
-30 - - - - - - 0.95 0.94 0.93 0.92