Installation
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Charging the refrigerant under conditions of liquid by using a liquid pipe
R-32 is a mixed type of refrigerant. It is necessary for recharging under conditions of liquid. When recharging
refrigerant from the refrigerant cylinder to the equipment, follow the instructions below.
Before recharging, check whether the cylinder has a siphon or not. There are two ways to recharge the
refrigerant.
Cylinder with siphon Cylinder without siphon
siphon
Charge the refrigerant standing the
cylinder upright.
Charge the refrigerant turning the
cylinder upside down.
NOTE
If R-32 refrigerant is charged with gas, the composition of the charged refrigerant changes and the
characteristics of the equipment vary.
During the measuring operation of refrigerant quantity added use an electronic balance.If cylinder doesn’t have
syphon, upset it.
Calculating the quantity of refrigerant to add
The quantity of additional refrigerant is variable according to the installation situation. Thus, make sure the outdoor
unit situation before adding refrigerant. This operation can only be performed by a qualified refrigeration specialist.
When installing the outdoor unit only
Model
Interconnection pipe length (m)
0 to 5 5 to 10 10 to 15 15 to 20 20 to 30 30 to 40 40 to 50
AC026RXADKG
AC035RXADKG
0 0 0 0
AC052RXADKG
0 0
+ 15 g/m over 10m
AC071RXADKG 0 + 25 g/m over 15m
Model
Interconnection pipe length (m)
0~30 30~40 40~50 50~60 60~70 70~75
AC100RXAD*G
AC120RXAD*G
0 +50 g/m over 30 m - - -
AC140RXAD*G 0 +50 g/m over 30 m