Module (Premium compact type)
Capacity
Model
Power Supply Voltage Range Nominal Running
Current [A]
Current [A]
Hz Voltage
Min.
(-10%)
Max.
(+10%)HP kW Cooling Heating MCA MFA
38 106.4 AM380MXWANR1 50/60 380~415 342 456 32.6 33.1 64.1 75
40 112.0 AM400MXWANR1 50/60 380~415 342 456 34.5 34.9 64.1 75
42 117.6 AM420MXWANR1 50/60 380~415 342 456 36.7 36.9 68.0 75
46 128.8 AM460MXWANR1 50/60 380~415 342 456 38.8 39.7 80.2 90
48 134.4 AM480MXWANR1 50/60 380~415 342 456 40.7 41.5 80.2 90
50 140.0 AM500MXWANR1 50/60 380~415 342 456 43.7 43.9 79.8 90
52 145.6 AM520MXWANR1 50/60 380~415 342 456 44.8 45.3 84.1 100
54 151.2 AM540MXWANR1 50/60 380~415 342 456 47 47. 3 88.0 100
58 162.4 AM580MXWANR1 50/60 380~415 342 456 49.9 50.5 95.9 125
60 168.0 AM600MXWANR1 50/60 380~415 342 456 52.8 53 96.0 125
62 173.6 AM620MXWANR1 50/60 380~415 342 456 54 54.3 99.8 125
68 190.4 AM680MXWANR1 50/60 380~415 342 456 59 59.6 112.1 125
70 196.0 AM700MXWANR1 50/60 380~415 342 456 60.9 61.4 112.1 125
80 224.0 AM800MXWANR1 50/60 380~415 342 456 70.1 70.4 127.8 150
90 252.0 AM900MXWANR1 50/60 380~415 342 456 79.2 79.5 144.0 175
NOTE
MCA: Mimium circuit amperes
MFA: Maximum fuse amperes
Select wire size based on the value of MCA