Water Flow rate
Section
Water Flow Rate (LPM)
8HP 10HP 12HP 20HP 30HP
Standard
condition
80 96 114 190 285
Operation range 48~96 58~115 68~137 114~228 170~342
80
70
60
50
40
30
20
10
0
80
70
60
50
40
30
20
10
0
0 50.0 100.0 150.0
Water Flow rate of cooling water (L/min)
Pressure Drop from plate type heat
exchanger (kPa)
AM080MXWA∗
AM100MXWA∗
AM120MXWA∗
90
80
70
60
50
40
30
20
10
0
90
80
70
60
50
40
30
20
10
0
0 10050 200150 250
Water Flow rate of cooling water (L/min)
Pressure Drop from plate type heat
exchanger (kPa)
AM200MXWA∗∗
Water Flow rate of cooling water (L/min)
Pressure Drop from plate type heat
exchanger (kPa)
70
60
50
40
30
20
10
0
0 200100 300 400
70
60
50
40
30
20
10
0
AM300KXWA∗∗
NOTE
• When the water flow rate is out of the operation range, stop the outdoor unit and take care of the cause
before restarting the operation. (Allowable range: 60~120% of the standard water flow rate)
• For the piping work, set the pump capacity considering the pressure drop of the plate heat exchanger to maintain a
proper flow rate.
8. Operating Range