- Press the key p to move to the next sensor “IN2 Type” and follow the adjustment
procedure of the first sensor
Los valores de fabrica de las sondas 2 y 3 son los siguientes:
SENSOR 2 SENSOR 3
IN2 Type=CO2(mA) IN3 Type=TEMP(V)
IN2 RANGE=2000PPM IN3 RANGE=50ºC
IN2 SET=1000PPM IN3 SET=27ºC
IN2(+/-)=1000PPM IN3(+/-)=5ºC
S2 ALARM=90%(PPM) S3 ALARM=90%(ºC)
MINI/MAXI” mode
In this mode, the CONTROL ECOWATT is set up to work with one, two or three contacts (J12,
J13 and J14) of the normally open (NO) or normally closed (NC) type. The CONTROL
ECOWATT functions in accordance with the first input that changes the setting and moves to
maximum speed. The sensors or external contacts are connected in the inputs E1(J12),
E2(J13) and E3(J14).
To change contact setting
- Press any of the 4 keys on the front panel.
- “IN1 OFF (NO)” appears on the display. This parameter indicates that the contact is in its
normal open position. Use keys - o + to change to NC (factory setting: NO)
- Press the key to p move to the next inputs “IN2and “IN3” and follow the same
procedure for each input. (factory setting: EN2: OFF(NO) – EN3:OFF(NO)).
CONTROL ECOWATT resetting
- Press the keys - and + simultaneously during 5 seconds untilRESET” appears on the
display, which allow to load all the factory setting values.
Restore defaults
& Reset? NO
- Press the key + to confirm the resetting operation for all the variables.
Restore defaults
& Reset? YES
This resetting operation needs a two-confirmation operation before to be acheived .
Press the key p to confirm the reset operation.
Output
input
P
MAX output
MIN output
Maximum speed
Minimum speed