Design
D - 39
Bolt span
Short direction(l
1
)
l
1
=㩷㩷1,000 mm ………..70, 90 type 1,000
120, 150, 190 type 1,000
Long direction(l
2
)
l
2
=㩷㩷1,060 mm ………..70, 90 type 1,060
120, 150, 190 type 1,060
Actual strength of the foundation bolts
Short term allowable tensile stress(f
t
)
f
t
= 176 㩷㩷N/mm
2
for SS400 f
t
:176
Short term allowable shear stress (f
s
)
f
s
= 99 㩷㩷N/mm
2
for SS400 f
s6
:132×0.75
Pull out load on one bolt
Short direction(R
b1
)
R
b1
=㩷㩷 = 1,614 N
Long direction(R
b2
)
R
b2
=㩷㩷 㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷= 1,473 N
Foundation bolt shear stress(
)
=㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷= 15.6㩷㩷N/mm
2
Foundation bolt tensile stress
Short direction(
1
)
1
=㩷㩷㩷㩷㩷㩷㩷㩷
㩷㩷
= 14.3㩷㩷N/mm
2
Long direction(
2
)
2
=㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷= 13.0 N/mm
2
Allowable tensile stress in a bolt subject to simultaneous tensile and shear stress(f
ts
)
f
ts
=1.4 f
t
-1.6 = 221.4 N/mm
2
Judgment
Tensile load
Short directionif R
b1
<T
a
OK R
b1
= 1,614 < T
a
= 11,760
Long directionif R
b2
<T
a
OK R
b2
= 1,473 < T
a
= 11,760
Shear stress
if < f
s
OK = 15.6 < f
s
= 99
Tensile stress
short direction if
1
< f
t
< f
t
= 176
㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷 㩷㩷㩷㩷 OK
1
= 14.3
㩷㩷㩷㩷㩷㩷
1
< f
ts
< f
ts
= 221.4
Long directionif
2
< f
t
< f
t
= 176
㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷 㩷㩷㩷㩷 OK
2
= 13.0
㩷㩷㩷㩷㩷㩷
2
< f
ts
< f
ts
= 221.4
F
H
h
h
G
–(W - F
V
)
l
G1
l
1
n
1
F
HG
- (W -F
V
)
l
G2
l
2
n
2
F
H
NA
R
b1
A
R
b2
A
11
12
3
δ
δ
δ
δ
δ
δ
τ
τ
τ
δδ
δδ
ττ
7. Center of gravity position and earthquake resistant design