16 °C
20 °C
24 °C
16 °C
20 °C
24 °C
1-7. Capacity Correction Graph According to Temperature Condition
SPW-C486/606VH8 (For 50 Hz and 60 Hz)
Outdoor unit heating capacity correction cof cient during frosting/defrosting (RH approximately 85%)
Outdoor intake air
temperature
°C WB (85% RH)
-20 -15 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6
Correction coef cient
1.0 1.0 0.97 0.96 0.96 0.95 0.94 0.91 0.89 0.88 0.87 0.87 0.87 0.88 0.89 0.91 0.92 0.95 1.0
To calculate the heating capacity with consideration for frosting/defrosting operation, multiply the heating capacity
found from the capacity graph by the correction coef cient from the table above.
Input coef cient (%) Capacity coef cient (%)
Outdoor air intake temp ( °C DB)
Cooling capacity ratio (maximum capacity) Heating capacity ratio (maximum capacity)
Input coef cient (%) Capacity coef cient (%)
Outdoor air intake temp ( °C DB)
Indoor air intake temp ( °C DB)
Indoor air intake temp ( °C DB)
Indoor air intake temp ( °C WB)
Indoor air intake temp ( °C WB)
SM830160-03ClassicPAC-iA4.ind295295SM830160-03ClassicPAC-iA4.ind295295 2010/02/1610:26:422010/02/1610:26:42