EasyManua.ls Logo

Sanyo SPW-C703GYH8 - Page 17

Sanyo SPW-C703GYH8
235 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ECO MULTI SYSTEM Unit Specifications
SM830052
I-11
1
1. Outdoor Unit
Outdoor Unit (C)
– 1. 5
MODEL No. SPW – C903GYH8 / SPW – C903GY8
Source 380 - 400 - 415 V / 3 phase / 50Hz
Controller P.C.B. Ass’y CR - C703GYH / CR - C703GY
Control circuit fuse 250 V , 3.15 A
Compressor Rotary (Hermetic)
PC (Power Control) AC (Standard)
Model … Code No. C-5R433H8U ... 80843688 C-5R433H8A ... 80843588
Nominal output kW 4.3 4.3
Compressor oil (SUNISO 4GSD-T) cc 2,000 2,000
Coil resistance V - U: 2.76 , U - W: 2.59 V - U: 2.76 , U - W: 2.59
(Ambient temperature 25°C) W - V: 2.71 W - V: 2.71
Safety devices
Thermal protector ON / OFF °C 120 ± 5 / 98 ± 11 120 ± 5 / 98 ± 11
Microprocessor safety devices Compressor current detection circuit
Compressor discharge gas temperature control
Defective and negative phase detection circuit
Voltage drop detection circuit
Crank case heater V, W 240 , 32 240 , 32
Fusible plug (Operating temp.) °C 73 ± 2
High pressure switch ACB - 1TB04W (TUV Approved)
Set pressure ON / OFF kg/cm
2
24 ± 2.0 / 30
+ 0
Fan (Number … diameter(mm)) Propeller (1 … ø 750)
Fan motor
Model … Nominal output W KFS8T - 201C3P … 200W
No. of pole … r.p.m. (230 V, High) 8 … 567 r.p.m.
Coil resistance BRN - WHT : 9.42
WHT - VLT : 4.59
VLT - YEL : 5.85
(Ambient temperature 20 °C) YEL - PNK : 3.33
Safety device
Thermal protector ON / OFF °C 125 – 15 / 130 ± 5
Run capacitor VAC , µF 440 V , 15.0 µF
Heat exchanger
Coil Aluminum plate fin / Copper tube
Rows … fin pitch mm 2 … 1.7
Face area m
2
2.40

Table of Contents