EasyManua.ls Logo

Sanyo SPW-CR363GVH8 - Page 18

Sanyo SPW-CR363GVH8
262 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ECO MULTI SYSTEM Unit Specifications
SM830063
I-13
1
1. Outdoor Unit
Outdoor Unit (C)
MODEL No. SPW – CR703GVH8 / SPW – CR703GV8
Source 380 - 400 - 415 V / 3 phase / 50Hz
Controller P.C.B. Ass’y CR - CR703GVH / CR - CR703GV
Control circuit fuse 250 V , 3.15 A
Compressor Rotary (Hermetic)
PC (Power Control) AC (Standard)
Model … Code No. C-5RN373H8R ... 80838788 C-5RN373H8C ... 80838588
Nominal output kW 3.75 3.75
Compressor oil (ETHER FV68S) cc 2,000 2,000
Coil resistance V - U: 2.83 , U - W: 2.65 V - U: 2.83 , U - W: 2.65
(Ambient temperature 25°C) W - V: 2.78 W - V: 2.78
Safety devices
Thermal protector ON / OFF °C 120 ± 5 / 98 ± 11 120 ± 5 / 98 ± 11
Microprocessor safety devices Compressor current detection circuit
Compressor discharge gas temperature control
Defective and negative phase detection circuit
Voltage drop detection circuit
Crank case heater V, W 240 , 32 240 , 32
Fusible plug (Operating temp.) °C 73 ± 2
High pressure switch ACB - 1TB14W (TUV Approved)
Set pressure ON / OFF kg/cm
2
23.5 ± 2.0 / 31.4
+ 0
Fan (Number … diameter(mm)) Propeller (1 … ø 750)
Fan motor
Model … Nominal output W KFJ8T - 301B3P … 300 W
No. of pole … r.p.m. (230 V, High) 8 … 576 r.p.m.
Coil resistance BRN - WHT : 11.89
WHT - VLT : 4.156
VLT - YEL : 9.639
(Ambient temperature 20 °C) WHT - PNK : 12.51
Safety device
Thermal protector ON / OFF °C (115 ± 5) / 130 ± 5
Run capacitor VAC , µF 400 V , 15.0 µF
Heat exchanger
Coil Aluminum plate fin / Copper tube
Rows … fin pitch mm 2 … 1.7
Face area m
2
2.40
– 1. 5