1. Specifications
1
MODEL No. SPW-T253GH56
Source 220 - 230 - 240 V / 1 phase / 50 Hz
Remote Controller (option) RCS - SH80TG (Microprocessor)
Controller P.C.B. Ass’y CR - X253GH (Microprocessor)
Fan (Number…diameter) mm Centrifugal (4...ø130)
Fan Motor
Model…Nominal output W KFG4Q - 41A5P...40 W
Source 220 - 230 - 240 V / 1 phase / 50 Hz
No. of pole…r.p.m. (230 V, High) rpm. 4...1,198
Coil resistance BRN WHT : 175.1 , ORG YEL : 70.9
(Ambient temperature 20 °C) WHT VLT : 43.6 , YEL PNK : 15.6
VLT ORG : 27.0
Safety device
Operating temperature Open °C 130 ± 5 °C
Close °C Differential 15 deg. (min.)
Run capacitor VAC, µF 440 V, 2.5 µF
Electronic refrigerant control valve
Solenoid control model DKV - MOZS550E0
Coil resistance (at 20 °C) ORG GRY : 46 , YEL GRY : 46
RED GRY : 46 , BLK GRY : 46
Solenoid control valve model IKV - 24D12
Heat exchanger
Coil Aluminum plate fin / Copper tube
Rows…fin pitch mm 3…1.7
Face area m
2
0.170
Auto louver motor MC8 D
Auto louver motor...Raterd V, Hz, W, rpm. 220 - 240 VAC, 50 Hz, 3 W, 3.3 rpm. 8P
Coil resistance (at 25 ˚C) 14,900 ± 8 %
Dew proof heater V, W 240 V, 15 W