– 9 –
SM830034
1
1. Specifications
1
1. Specifications
1-1 Unit Specifications
MODEL No. Indoor Unit SPW-T253GH56
Outdoor Unit SPW-C253GH8
POWER SOURCE 380 - 400 - 415 V / 3N / 50 Hz
PERFORMANCE Cooling Heating
Capacity kW 7.3 8
BTU / h 25,000 27,000
Air circulation (Hi/Me/Lo) m3 / h 1,140/1,020/840
Moisture removal(High) Liters/h 3.4 -
ELECTRICAL RATINGS
Voltage rating V 380 400 415 380 400 415
Available voltage range V 342 - 456 342 - 456
Running amperes* A 4.8 4.6 4.5 4.9 4.8 4.7
Max. running amperes** A 5.3 5.1 4.9 5.7 5.5 5.3
Power input kW 2.72 2.74 2.77 2.81 2.82 2.85
Power factor % 86.1 86 85.6 87.1 84.8 84.4
C.O.P W / W 2.68 2.66 2.64 2.85 2.84 2.81
Max. starting amperes A 26 28 29 26 28 29
FEATURES
Controls / Thermostat control Microprocessor / I.C. thermostat
Timer ON / OFF 72-hours / ON/OFF 24-hours & Program
Fan speeds Indoor/Outdoor 3 and Automatic control/ 2 (Auto)
Airflow direction (Indoor) Automatic (Remote control)
Air filter Washable, easy access
Remote controller (Option) Wired:RCS-SH80TG / Wireless:RCS-SH80TGWL
Refrigerant control Electronic Refrigerant Control Valve
Drain pump (drain connection) No (20A, OD26mm)
Compressor Rotary
Operation sound Indoor - Hi/Me/Lo dB - A 45 / 41 / 37
Outdoor - Hi dB - A 52
REFRIGERANT TUBING
Limit of tubing length m (ft.) 50 (164)
Limit of tubing length at shipment m (ft.) 30 (98)
Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit: 50 (164)
between the two units
Outdoor unit is lower than indoor unit: 30 (98)
Refrigerant tube Narrow tube mm (in) 6.35 (1 / 4)
outer diameter Wide tube mm (in) 15.88 (5 / 8)
Refrigerant amount at shipment kg R22 - 3.0
DIMENSIONS & WEIGHT Indoor unit Outdoor unit
Unit dimensions Height mm (in) 185 (7-9/32) 735 (28-30/32)
Width mm (in) 1,270 (50) 940 (37)
Depth mm (in) 670 (26-12/32) 340 (13-12/32)
Package dimensions Height mm (in) 271 (10-21/32) 826 (32-17/32)
Width mm (in) 1,370 (53-30/32) 1,016 (40)
Depth mm (in) 782 (30-25/32) 416 (16-12/32)
Net weight kg (lb) 28 (62) 71 (157)
Shipping weight kg (lb) 36 (79) 77 (170)
Shipping volume m
3
(Cu. ft.) 0.29 (10.2) 0.349 (12.3)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Cooling :
Rating conditions(*) : Indoor air temperature 27
°
C DB / 19
°
C WB, Outdoor air temperature 35
°
C DB
Full load conditions(**) :Indoor air temperature 35
°
C DB / 25
°
C WB, Outdoor air temperature 45
°
C DB
Heating :
Rating conditions(*) : Indoor air temperature 20
°
C DB, Outdoor air temperature 7
°
C DB / 6
°
C DB
Full load conditions(**) :Indoor air temperature 24
°
C DB, Outdoor air temperature 24
°
C DB / 15.5
°
C WB