EasyManua.ls Logo

Sanyo SPW-X253GH56 - 1-2 Major Component Specifications

Sanyo SPW-X253GH56
105 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
– 12 –
SM830033
1. Specifications
1
1-2 Major Component Specifications
(A) Indoor Unit
MODEL No. SPW-X253GH56
Source 220 - 230 - 240 V / 1 phase / 50 Hz
Controller P.C.B. Ass’y CR - X253GH (Microprocessor)
Fan (Number…diameter) mm Turbo (1...ø490)
Fan Motor
Model…Nominal output W SFG6X - 41A5P...40 W
Source 220 - 230 - 240 V / 1 phase / 50 Hz
No. of pole…rpm(230 V, High) rpm. 6...470
Coil resistance BRN WHT : 114.0 , ORG YEL : 66.4
(Ambient temperature 20°C) WHT VLT : 23.9 , WHT PNK : 77.4
VLT ORG : 12.4 , YEL BLK : 82.1
Safety device
Operating temperature Open °C 130 ± 8 °C
Close °C 79 ± 15 °C
Run capacitor VAC, µF 440 V, 4µF
Electronic Refrigerant Control Valve
Solenoid control model DKV - MOZS582E0
Coil resistance (at 20°C) ORG GRY : 46 , YEL GRY : 46
RED GRY : 46 , BLK GRY : 46
Solenoid control valve model IKV - 24D12
Heat exchanger
Coil Aluminum plate fin / Copper tube
Rows…fin pitch mm 2…1.7
Face area m
2
0.295
Panel
Model No. PNR - X253GHA
Dew proof heater 240 V, 26 W
Auto louver motor M2LB24ZA12
Auto louver motor...Rated V, W, rpm. AC 240 V, 3W, 2.5 rpm
Coil resistance (at 25 °C) 15,620 ± 15%
Drain Pump WP20SL - 21
Rated V, W AC 230 V, 50 Hz, 14.7 W
Total head & capacity 400 mm, 600 cc/min

Table of Contents