7.First heating cycle rate
Parameter options:(FA,SL)
FA: Fast rate, heating will activate 0.6℉below set point
SL: Slow rate, heating will activate 1.2℉below set point
Factory default:FA
8.First cooling cycle rate
Parameter options:(FA,SL)
FA: Fast rate, cooling will activate 1.2℉abvoe set point
SL: Slow rate, cooling will activate 1.7℉above set point
Factory default:FA
9.Emergency heat cycle rate
Parameter options:(FA,SL)
FA: Fast rate, Emergency will activate 1.2 ℉below set point
SL: Slow rate, Emergency heat will activate 1.7℉below set point
Factory default:FA
This option apply only to HP1 or HP2 setting in system type option
10.Compressor lockout delay option
Parameter options:(0,5)
To protect the compressor from short cycling, you can select compressor off-time cycle
between 0 or 5 minutes
Factory default:5
When the thermostat compressor time delay occurs, “Comp Dly” display during compressor
lockout.
11.Display backlight option
Parameter options:(1,2,3)
1:No backlight display
2:The backlight come on for approximately 30s when any button is touched
3:The backlight remain on continuously
Factory default:2
When operated from batteries (No “C” terminal connection, or if AC power goes off), the
LCD continuously display of backlight will be disabled.)