4
System description and installation
CA-64 SATEL
Expander for the proximity card reader or DALLAS chip reader
♦ one or two reading heads (entrance and exit registration),
♦ relay for electromagnetic door lock control,
♦ zone used for monitoring the relay (NC),
♦ zone used for monitoring the door status (NC),
♦ additional zone for monitoring the module tampering (NC).
Zone module
♦ 8 zones with properties identical to the main panel zones.
♦ Additional zone for monitoring the module tampering.
Output module
♦ 8 outputs with functional properties identical to the main panel outputs in three
versions: 8 relay outputs, 8 outputs of OC type or 4 relay outputs/ 4 OC type
outputs.
♦ Zone for monitoring the module tampering.
Zone module with power supply unit
♦ 8 zones with properties identical to the main board zones.
♦ Additional zone for monitoring the module tampering.
♦ Pulse power unit, output load 2.2 A, with short circuit protection.
♦ Battery charging and control circuit with disconnecting the discharged battery.
Output module with power supply unit
♦ 8 outputs with functional properties identical to the main board outputs in three
versions: 8 relay outputs, 8 outputs of OC type or 4 relay outputs/ 4 OC type
outputs.
♦ Zone for monitoring the module tampering.
♦ Pulse power unit, output load 2.2 A, with short circuit protection.
♦ Battery charging and control circuit with disconnecting the discharged battery.
Addressable zones expander
♦ bus (3 wires) for connecting up to 48 addressable modules operating with typical
detectors, mounted directly to the detector casing; the detector with addressable
module mounted to it is referred to as “addressable detector”,
♦ additional zone for monitoring the module tampering,
♦ Pulse power unit, output load 2.2 A, with short circuit protection.
♦ Battery charging and control circuit with disconnecting the discharged battery.
Voice synthesiser expander
♦ memory module for storing 16 verbal messages, 15 seconds per each message.