4. Installation of the flue
4.1 PVC Venting Method
The KDB-GOM Series boiler may be vented using 75mm schedule-40 venting materials.
Cut all lengths of pipe cleanly maintaining a 90-degree square edge. Use long radius elbows whenever possible.
Use only the type of adhesive recommended by the stainless pipe manufacturer.
Keep an uphill slant from boiler to the outside to ensure that all condensed water inside the pipe will return back to
the boiler.
Do not place the outdoor termination kit in an area where discharge gasses will be directed towards evergreen
shrubbery.
Assemble the flue using the following illustration as a guide. Your installation may vary slightly from the illustration
shown below.
Use the optional Vent Termination Kit for venting the KDB-GOM boiler to outside area.
Use the optional Vent Termination Kit for venting the KDB-GOM boiler to outside area.Use the optional Vent Termination Kit for venting the KDB-GOM boiler to outside area.
Use the optional Vent Termination Kit for venting the KDB-GOM boiler to outside area.
- Standard : The Stainless Steel Concentric Flue Kit for KDB-GOM models.
“A” : 75
㎜×
㎜×㎜×
㎜×
1.0m LENGTH STAINLESS FLUE PIPE
“B” : 75
㎜×
㎜×㎜×
㎜×
0.5m LENGTH STAINLESS FLUE PIPE
“C” : 75
㎜×
㎜×㎜×
㎜×
90-DEG. STAINLESS ELBOW
Shown : 75
(3
) Stainless Venting.
“C”
“A” or “B”
(Maximum Allowable
Flue Length = 5 m)
Min. 250
(10
)
Vent Termination Kit
Exhaust
Intake Air
Min. 600
(2 ft) from ground
(Note! - Install the vent termination kit in an
area away from plants,
people and
animals)
φ
75
(3
)
Type 304
stainless steel
only
NOTE
) Intake Air :
φ
75
(3
) stainless steel.
) Exhaust :
φ
75
(3
) Stainless steel.
) Maximum three 90
°
elbows.
) Slant flue pipe 2-3
°
away from boiler to outside,
to drain condensate.
Ground
KDB-GOM
BOILER
“C”
To Drain
Install Horizontal Drip
Tee
If Required