CHARACTERISTICS
Operating mechanism
type MR41E
ENGLISH
USE OF THE OPERATING MECHANISM IN SINGLE POLE OPERATED MODE
This operating mode is used when the 3P disconnector poles are not mechanically inter-connected. Three MR41E electrical
operating mechanisms are used (one operating mechanism, referred to as the MASTER, controls the two others referred to as
SLAVES), one on each pole and electrically inter-connected by an S-COM communication module.
The remote control orders are managed by the master, who then redirects them to the two slaves, via the S-COM module.
Each MR41E single pole operated electrical operating mechanism has a digital display that reports any single pole operated
mode faults.
The main faults are displayed on the master, and the secondary faults on each slave.
To acknowledge a fault :
1
2
1 2
To accept remote control orders, each MR41E electrical operating mechanism must:
- have its position selector on the REMOTE mode
- be in the same position as the Master (Open or Closed)
- have no current blocking faults on a disconnector.
If this is not the case (for example a slave has its selector in the local position), the master
detects that the operating condition is not nominal and will not accept orders. It will display a
fault that will make the single pole operated mode not usable.
i
Signalling Contacts
S-COM Module
Position selector
Leds
0 and l buttons
S-DIGIT digital display
Set the SELECTOR to manual
Then return to the original mode,
in the example opposite, via the
REMOTE mode.