MR-2100/2200 Operator’s Manual
10
2.0 Supplementary Information
2.1 Condition Codes and Zone Numbers
The History and Archive use the following formats for condition codes and zone numbering.
Condition Code
Archive
Alarm List Description
A ALARM Alarm
B bypass Bypass
C com Comlink
D dupl Duplicate Addressable Device
E alert Maintenance Alert
G ground Ground Fault
H Hot Key Pressed
I ilgl Illegal Addressable Device
J Switch
M msng Missing Addressable Device
N nofire Non-Fire/Non-Reporting
P M.PULL Pull Station Alarm
S spv Supervisory
T trbl Trouble or Parameter Change
U wrong Wrong Device Type
W WFLOW Waterflow Alarm
A plus sign (+) refers to a new or on condition, a minus sign (-) refers to a restoration or off
condition, and an equal sign (=) refers to a one time event.
Zone Number
PPP:ZZ.SSS Format:
PPP Control Panel Number
ZZ Panel Zone
Notes:
Panel
Zone
Description
Panel
Zone
Description
0 General Alarm 81 1st Stage Alarm
1 Initiating Circuit 1 82 2nd Stage Alarm
2 Initiating Circuit 2 83 Switch
50 Network Verify 84 Test Mode
51 Comlink 1
85
1
Erase Configuration
52 Comlink 2
86
3
Change Configuration
53 Comlink 3 87 Passcode Tamper
54 Comlink 6
88
1
Database Loaded
60 Output (bell) Supervision
89
1
Time/Date Change
61 Auxiliary Power Supervision
90
1
Hot Key Activation
64
1
Program Checksum
91
1
Memory Overflow
65
1
Database Checksum
92
1
Network Reboot
66 AC Power
93
1
New Program
67 Low Battery
94
1
Network Reboot Required who
69
1
Program Restart
95
1
Network Reboot Required why
80
2
Privilege Level

Other manuals for Secutron MR-2100