MR-2900 Installation Manual
31
7.0 Appendix C: UL Listed Compatible Devices
7.1 UL Listed “Class B” Smoke Detectors
The following Listed 2-wire smoke detectors and bases are compatible with the MR-2900 Control Panel
using the MR-2928 Conventional Input Circuit Modules (with compatibility identifier MR-2928). Up to 5
μA
of smoke detector normal standby load may be connected to MR-2928 conventional initiating device
circuit.
Manufacturer
Smoke
Detector
Model
Base
Identifier
Model
Standby
Identifier
Current
System Sensor 1400 A N/A N/A 100 μA
1451 A B401 A 120 μA
1451 A B401B A 120 μA
2300T A N/A N/A 120 μA
2300TB A N/A N/A 120 μA
2400 A N/A N/A 120 μA
2400TH A N/A N/A 120 μA
2451 A B401 A 120 μA
2451 A B401B A 120 μA
2451 A DH400 A 120 μA
2451TH A B401 A 120 μA
2451TH A B401B A 120 μA
Apollo 55000-250 55000-250 45681-200 45681-200 59 μA
55000-250 55000-250 45681-230 45681-230 80 μA
55000-250 55000-250 45681-231 45681-231 80 μA
55000-350 55000-350 45681-200 45681-200 110 μA
55000-350 55000-350 45681-230 45681-230 130 μA
55000-350 55000-350 45681-231 45681-231 130 μA
Cerebrus DI-3C
Pyrotronics DI-4
DI-4B
PEC-3
Detection Systems DS200 A MB200-2W A 80 μA
DS200HD A MB200-2W A 80 μA
Edwards 6250B 001 6251B 001 30 μA
6270B 001 6251B 001 50 μΑ