Rev B Doc. 6001036 Page 9 of 20
ACTIVATION TIME FOR RELAY 2 __ 08 + ENTER --ANSWER MUST ALSO CONTAIN 2
DIGITS.
--IF THIS RELAY ACTIVATES A GATE
OPERATOR WITH A MOMENTARY
CONTACT CLOSURE, YOU WILL
NEED TO SET THE RELAY
ACTIVATION TIME FOR A SHORT
PERIOD OF TIME (FOR EXAMPLE, 2
SECONDS). IF YOU SET THE
RELAY ACTIVATION TIME FOR A
LONGER PERIOD OF TIME, THERE
IS A POSSIBILITY THAT THE GATE
WILL CONTINUE TO OPEN AND
CLOSE UNTIL THE RELAY
ACTIVATION PERIOD HAS ENDED.
--IF THE RELAY CONFIGURATION
FOR RELAY 2 IS SET FOR CCTV
IMMEDIATE AND YOU WISH TO
HAVE RELAY 2 DEACTIVATE ONCE
THE CALL IS TERMINATED (BY
EITHER GRANTING OR DENYING
ACCESS TO THE BUILDING OR THE
CALL “TIMING OUT”), THEN SET
THE RELAY ACTIVATION TIME FOR
01 SECOND. IF YOU WISH TO HAVE
THE ABILITY TO WATCH SOMEONE
ENTER THROUGH THE GATE, THE
RELAY ACTIVATION TIME SHOULD
BE SET FOR A LONGER PERIOD OF
TIME.
AREA 03 - SETTING STRIKES-AND-OUT
PURPOSE: Specifies the number of wrong codes that can be entered consecutively before a unit stops
accepting codes for 3 minutes and will close a specified relay. Factory setting = 3 incorrect
entries.
SYSTEM PROMPT
EXAMPLE OF
TYPICAL ENTRY
IMPORTANT NOTES
ENTER NUMBER OF STRIKES (1-9) __ 4 + ENTER WILL ALLOW 4 INCORRECT CODES.
AREA 04 - SETTING CALL LENGTH
PURPOSE: Sets the length of any call made by the system. Time starts when dialing stops.
Factory setting = 60 seconds.
SYSTEM PROMPT
EXAMPLE OF
TYPICAL ENTRY
IMPORTANT NOTES
ENTER TALK TIME ___ SECONDS 072 + ENTER --ENTER TIME AS THREE DIGITS
--THIS ENTRY CAN BE BETWEEN 015
AND 250 SECONDS.