SHARP(CHINA) INVESTMENT CO., LTD 
6. DC Over Current Error 
 
 
 
 
 
 
 
      
            
 
 
 
 
 
 
 
 
     No 
   
 
   
No  
 
 
    
        
 
 
 
 
 
 
 
 
 
 
 
 
 
                No 
                      Heating mode 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
error memory isrecorded. 
Start 
Are valves(2-way and 
3-way) close? 
Does compressor rotate? 
Fully open stop valves 
Does compressor rotate more 
than 30 seconds?
 
Check IPM lead 
wire.(UVW) 
Check IPM short 
circuit. 
Check compressor 
terminal. 
Replace PWB 
Does compressor 
rotate? 
Replace Compressor 
Modify the connection of compressor 
lead wire on PWB. 
Replace P WB.
Modify compressor terminal marking. 
Yes  
Yes  
Abnormal  
Abnormal  
Abnormal  
Is IPM PWB floating  from the 
heat sink? 
No  
Check the AC power  supply 
voltage when compressor 
rotate.(rated voltage±10%) 
normal  
normal 
normal  
No  
Cooling mode? 
Check outdoor exchanger 
termistor and  discharge      
    thermistor. 
Modify or replace termistor. 
Check indoor exchanger 
thermistor and
  discharge   
      thermistor. 
Modify or replace termistor. 
Check indoor heat 
exchanger. 
normal 
Check outdoor heat 
exchanger. 
Clean indoor heat 
exchanger.
 
Clean indoor heat exchanger.
Check the refrigerant amount. 
Check the discharge pressure.  Check the installation condition. 
Fix IPM PWB with screws securely. 
Yes  
Yes  
normal 
Yes  
Abnormal 
Abnormal 
normal 
3-9