[4] HOW TO OPERATE THE OUTDOOR UNIT INDEPENDENTLY
1. Cooling in 40 Hz fixed mode
To operate the outdoor unit independently, short-circuit the sections indicated by arrows in the diagram below with an adapter, and apply 230 VAC
between (1) and (N) on the terminal board of the outdoor unit. This allows the outdoor unit to be operated in cooling mode independently.
(Do not operate the outdoor unit in this condition for an extended period of time.)
[5] GENERAL TROUBLESHOOTING CHART
1. Indoor unit does not turn on
2. Indoor unit fan does not operate
3. Indoor unit fan speed does not change
4. Remote control signal is not received
Main cause Inspection method Normal value/condition Remedy
Cracked PWB.
(Cracked pattern)
Check visually. There should be no cracking in 
PWB or pattern.
Replace PWB.
Open-circuit in FU1 (250 V, 3 A), 
FU2 (250 V, 3 A)
Check melting of FU1, FU2. There should be no open-circuit. Replace PWB.
Main cause Inspection method Normal value/condition Remedy
Open-circuit in heat exchanger 
thermistor (TH2) (in heating oper-
ation)
Measure thermistor resistance 
(dismount for check).
See on page 8- Replace thermistor.
There should be no open-circuit 
or faulty contact.
Replace thermistor.
Disconnected heat exchanger 
thermistor (TH2) (in heating oper-
ation)
Inspect connector on PWB.
Check thermistor installation con-
dition.
Thermistor should not be discon-
nected.
Install correctly.
Main cause Inspection method Normal value/condition Remedy
Remote control not designed to 
allow fan speed change.
Check operation mode. Fan speed should change except 
during dehumidifying operation, 
ventilation, light dehumidifying 
operation, internally normal oper-
ation
Explain to user.
Main cause Inspection method Normal value/condition Remedy
Batteries at end of service life. Measure battery voltage. 2.5 V or higher (two batteries in 
series connection)
Install new batteries.
Batteries installed incorrectly. Check battery direction. As indicated on battery compart-
ment.
Install batteries in indicated direc-
tion.
Lighting fixture is too close, or flu-
orescent lamp is burning out.
Turn off light and check. Signal should be received when 
light is turned off.
Change light position or install 
new fluorescent lamp.
Use Sevick light (Hitachi). Check if Sevick light (Hitachi) is 
used.
Signal may not be received 
sometimes due to effect of Sevick 
light.
Replace light or change position.
Operating position/angle is inap-
propriate.
Operate within range specified in 
manual.
Signal should be received within 
range specified in manual.
Explain appropriate handling to 
user.
(L2)
Short-circuit negative terminal of
capacitor (C33) and jumper wire
(JP16) using IC clip, etc.