EasyManuals Logo

Sharp AH-A129E User Manual

Sharp AH-A129E
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #20 background imageLoading...
Page #20 background image
AH-A129E
AU-A129E
20
TROUBLESHOOTING OF A CONTROL CIRCUIT
measure the secondary voltage
of transformer.
YES
NO
YES
NO
The machine does not function
at all with remote controller and
switches on the indoor unit.
Using a meter, measure the 
voltage between anodes of D1 
and D2 on the PWB ass'y 1.
Is the measured value 
approx. 20.6 Vac ?
Replace the PWB with a new 
one.
Is the 2.5A fuse 
open circuit ?
Replace the fuse and varistor 
with new ones.
Replace the transformer with
a new one.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sharp AH-A129E and is the answer not in the manual?

Sharp AH-A129E Specifications

General IconGeneral
BrandSharp
ModelAH-A129E
CategoryAir Conditioner
LanguageEnglish

Related product manuals