List of Parameters for Operating Condition
Function explanation:
1. Utility over voltage (Vac): Setting utility over voltage trigger value.
2. Utility under voltage (Vac): Setting utility under voltage trigger value.
3. Voltage abnormal trip time (sec): Setting trip time when over and under voltage
protection is triggered.
4. Utility over frequency (Hz): Setting utility over frequency trigger value.
5. Utility under frequency (Hz): Setting utility under frequency trigger value.
6. Freq. abnormal trip time (sec): Setting trip time when over and under frequency
protection is triggered.
7. Recover timer: Setting solar power conditioner recovery time when error occurrence.
8. RJ-45 ID: Setting RJ-45 ID number.
9. Operation frequency: Setting utility frequency.
Table2. Setting value and parameter (The shadow value is default setting.)
Item Function Parameters
1 Utility over voltage (Vac) 250 255 260
2 Utility under voltage (Vac) 205 210 215
3 Voltage abnormal trip time (sec) 1 1.4 1.8
4 Utility over frequency (Hz) 52 53 54
5 Utility under frequency (Hz) 46 47 48
6 Freq. abnormal trip time (sec) 1 1.4 1.8
7 Recover timer 10 60 150 300
8 RJ-45 ID 5 6 …… 31
9 Operation frequency 50 60