EasyManua.ls Logo

Sharp JW10 - WEBACCESS: PARAMETERS; WebAccess Parameters Overview; CONFIGURE A SHARP JW DEVICE; Summary of Configuration Steps

Sharp JW10
13 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Advantech WebAccess Device Driver Guide Sharp JW 10 Serial
Version 6.0 rev 0 Advantech Corp., Ltd. page 5
D5=0=1 bit;
D5=1=2 bits
D4,D3= Parity:
0,0 = None
0,1 = Odd
1,0 = Even
1,1 = Disabled
D2, D1, D0 = Transfer Rate (Bits / sec):
1,1,1 = 38400
0,0,0 = 19200
0,0,1 = 9600
0,1,0 = 4800
0,1,1 = 2400
1,0,0 = 1200
1,0,1 = 600
1,1,0 = 300
System Memory #237 sets the PLC Address: 001 to 077 (octal).
WebAccess would use decimal addresses: 1 to 63 (decimal).
2. WebAccess: Parameters
WebAccess drivers provide object-oriented "parameters" to guide novice
users with pre-built templates containing typical addresses and provide a
productivity tool for experienced users. Users can select a parameter type to
start, and then modify the address to the correct register in order to build a
tag.
Note 1 WebAccess cannot write reliably to a Register if Ladder Logic is also
writing to the same register. Ladder Logic executes more quickly that
WebAccess and will overwrite any write from WebAccess.
Note 2 The PLC must be in RUN mode for physical IO to be scanned by the
PLC and written to memory of PLC.
3. Configure a Sharp JW
device
3.1 Summary
1. Start Internet Explorer Web Browser.
2. Enter IP address of the Project Node.
3. Use WebAccess Configuration.
4. Open or Create a Project.
5. Configure a SCADA node (the PC that will connect to the automation
hardware).
6. Configure a Comport for the SCADA Node that is a Serial type