_________________________Shihlin Electric SPM-3 User Guide__________________
11
4.3 SettingMPE/TandV/A
To enter setting mode, pressMand V/Abuttons simultaneously. The setting mode is used for
basic operation, clear informal data and alarms setting
Mmoves cursor right ward like
Pmoves the cursor down ward likeor reduce one
E/Tmoves the cursor up ward likeor add one
V/Aconfirms the selection likeEnter, and turn to next page
MandV/Atogether moves back to the setting mode page or to the operation display
First, pressingMaV/Asimultaneously to enter password entering page, it requires 4 digits (default
0000).
PASS
WORD
0000
Then, select the setting fromBASICALARM+I/OCLEARby usedP
orE/T
P0
MAIN
MENU
BASIC / ALARM+I/O / CLEAR
4.3.1 General Setting (N)
N1: Address Setting from 1-255 (Default 15)
N1
Add
015
N2: BAUD RATE Setting - 4800, 9600, 19200, 38400, 57600. (Default 19200)
N2
BAUD
RATE
19200
N3: STOP BIT Setting - “1” or “2” (Default 1)
N3
STOP
BIT
1
N4: Wire Type Setting -1P2W1P3W3P3W-2CT3P3W-3CT3P4W-YAUTO (Default AUTO)
N4
WIRE
TYPE
3P4W
N5: PT Primary Setting from 60-600000 (Default 110)
N5
PT1
000110
N6: PT2 Secondary Setting from 1-600 (Default 110)
N6
PT2
110