_________________________Shihlin Electric SPM-3 User Guide__________________
11
4.3 Setting「M」、「P」、「E/T」and「V/A」
To enter setting mode, press「M」and 「V/A」buttons simultaneously. The setting mode is used for:
basic operation, clear informal data and alarms setting
「M」moves cursor right ward like「」
「P」moves the cursor down ward like「」or 「reduce one」
「E/T」moves the cursor up ward like「」or 「add one」
「V/A」confirms the selection like「Enter」, and turn to next page
「M」and「V/A」together moves back to the setting mode page or to the operation display
First, pressing「M」a「V/A」simultaneously to enter password entering page, it requires 4 digits (default
0000).
PASS
WORD
0000
Then, select the setting from「BASIC」、「ALARM+I/O」、「CLEAR」by used「P」
or「E/T」
P0
MAIN
MENU
BASIC / ALARM+I/O / CLEAR
4.3.1 General Setting (N)
N1: Address Setting from 1-255 (Default 15)
N1
Add
015
N2: BAUD RATE Setting - 4800, 9600, 19200, 38400, 57600. (Default 19200)
N2
BAUD
RATE
19200
N3: STOP BIT Setting - “1” or “2” (Default 1)
N3
STOP
BIT
1
N4: Wire Type Setting -1P2W,1P3W,3P3W-2CT,3P3W-3CT,3P4W-Y,AUTO (Default AUTO)
N4
WIRE
TYPE
3P4W
N5: PT Primary Setting from 60-600000 (Default 110)
N5
PT1
000110
N6: PT2 Secondary Setting from 1-600 (Default 110)
N6
PT2
110