Output 2 PID1 maximum limiter setting screen
 Initial value:100.0
 Setting range: output limiter lower limit values +0.1~100.0 %
key Contents is the same with output 1 PID1.
Output 2 PID2 proportional-band (P) setting screen
  Initial value:3.0%
 Setting range: OFF, 0.1 999.9%
key
Contents is the same with output 1 PID1.
Output 2 PID2 integral-time (I) setting screen
  Initial value: 120 seconds
 Setting range: 0FF, 1~6000 seconds
key Contents is the same with output 1 PID1.
Output 2 PID2 derivative-time (D) setting screen
 Initial value: 30 seconds
 Setting range: 0FF, 1~3600 seconds
key Contents is the same with output 1 PID1.
Output 2 PID2 dead-band setting screen
 Initial value:0.0
 Setting range:-50.050.0%
key Contents are the same as output 2PID1 dead-band setting screen.
Output 2 PID2 differential-gap setting screen
 Initial value: 5
Setting range: 1~999 digits
key
Contents is the same with output 1 PID1.
Output 2 PID2 minimum limiter setting screen
 Initial value: 0.0
 Setting range: 0.0~99.9%
key Contents is the same with output 1 PID1.
Output 2 PID2 maximum limiter setting screen
 Initial value:100.0
 Setting range:output limiter lower limit values+0.1~100.0 %
key Contents is the same with output 1 PID1.
Output 2 PID3 proportional-band (P) setting screen
  Initial value:3.0%
 Setting range:OFF, 0.1999.9%
key
Contents is the same with output 1 PID1.
Output 2 PID3 integral-time (I) setting screen
  Initial value: 120 seconds
 Setting range: 0FF, 1~6000 seconds
key
Contents is the same with output 1 PID1.
Output 2 PID3 derivative-time (D) setting screen
 Initial value: 30 seconds
 Setting range: 0FF, 1~3600 second
key Contents is the same with output 1 PID1.
Output 2 PID3 dead-band setting screen
 Initial value:0.0
 Setting range:-50.050.0%
key Contents are the same as output 2 PID1 dead-band setting screen.
Output 2 PID3 differential-gap setting screen
 Initial value:5
Setting range: 1~999 digits
key Contents is the same with output 1 PID1.
Output 2 PID3 minimum limiter setting screen
 Initial value:0.0
 Setting range: 0.0~99.9%
key Contents is the same with output 1 PID1.
Output 2 PID3 maximum limiter setting screen
 Initial value:100.0
 Setting range: output limiter lower limit values+0.1~100.0%
key Contents is the same with output 1 PID1.
Output 2 soft starting time setting screen
 Initial value:OFF
 Setting range:OFF, 0.5~120.0 seconds (setting resolution 0.5 second)
key
Contents is the same with output 1.
Output 2 proportional periodic-time setting screen
 Initial value: Contact output 30.0 seconds
 Voltage pulse output 3.0 seconds
key Setting range: 0.5~120.0 seconds (setting resolution 0.5 second)
Contents is the same with output 1.
Output 2 characteristics setting screen
 Initial value:
 Setting range:
key Contents is the same with output 1.
Return to mode 4 lead screen.
(8) Mode 5 screens
Mode 5 screens is the setup screens of event option. Not displayed when option is not added.
Mode 5 lead screen
 No setup.
Press key , it shifts to the first setting screen, event 1 operation-mode setting screen.
key
Event 1 operation-mode setting screen
 Initial value:
 Setting range: Chosen from event type character table.
key
Event type allotted to event 1 is chosen from character table.
Event type character table
Character
Type Character
Type
 No allotment  Control loop alarm 2

Upper limit absolute value
alarm
 Step signal

Lower limit absolute value
alarm
Pattern termination signal
 Scale over alarm  Program termination signal
 Maximum deviation alarm
 Hold signal
 Minimum deviation alarm  Program signal
 Within deviation alarm   Up slope signal
 Without deviation alarm   Down slope siganal
 RUN signal  Gurantee signal
 Control loop alarm 1
Being initialized if measuring range, scaling, and unit are changed.
Deviation alarm is possible to output at the time of RUN+AUTO.
In other events, output is always possible.
Event 1 differential-gap setting screen
 Initial value:5Digits
Setting range: 1~999 Digits
key ON-OFF differential gap of event 1 is set .
Not displayed, when the event 1 mode are as follows.
   .
Change in measuring range, scaling, unit, and the event 1 mode make it initialize.
Event 1 standby operation setting screen
  Initial value:
key Setting range::
No standby operation、 : standby-operation only at the time of a power-on.
Standby-operation in the following cases. ;At the time of power-on.
When each alarm's operating point is changed,
When deviation alarm's SV is performed,
When RUN/STBY (RST) is switched,
When AUTO/MAN is switched.
Not displayed, when the event 1 mode are as follows. ;
  .
Change in measuring range, scaling, unit, and the event 1 mode make it initialize.