EasyManua.ls Logo

Shini SIC-W Series - 2 Structural Features and Working Principle; Main Functions; Working Principle

Shini SIC-W Series
45 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
15(45)
2. Structural Features and Working Principle
2.1 Main Functions
SIC-W air-cooled water chillers include consists of four main components, which
are compressor, condenser, thermostatic expansion valve, and evaporator. The
system adopts single-stage vapour compressed refrigeration system, which uses
refrigerant gas-liquid conversion to absorb and release heat, thus achieving the
cooling effect.
2.1.1 Working Principle
1. Compressor
2. Tube-in-shell condenser
3. Fudible plug
4. Drying filter
5. Liquid pipe solenoid valve
(optional)
6. Refrigerant indicator(optional)
7. Expansion valve
8. Evaporator
9. Anti-freezing switch
10. Flow switch (option)
11. Water level liquid indicator
(option)
12. Temp. sensor
13. Water tank
14. Float ball switch
15. Pump
16. Water pressure gauge
17. By-pass valve
18. Sluice valve (for middle and high
pressure pump)
19. Hot-gas by-pass valve (option)
20. Pressure controller
Picture 2-1Working Principle Diagram
When the machine is started, compressor (1) starts working. Refrigerant is
compressed into high pressure and high temperature gas in the process from B to
C to enter the condenser 2 to exchange heat with the air, which changes from gas
to liquid and the heat is taken away by the air. In the C-D-E-F process, the liquid