User’s Manual 21
Conditions for its
activation
Fuel solenoid closed (“FUEL SOLENOID output, terminal 22
enabled)
“TEMPERAT. ALARM” digital input (terminal 09) shorted to
ground
Indicator “TEMPERATURE” slowly flashing
Parameter P46 = 0 and/or parameter P35 = 0
Conditions for its
activation
Fuel solenoid closed (“FUEL SOLENOID output, terminal 22
enabled)
Temperature detected from the “TEMPERATURE” analogue
input (terminal 43) over or equal to the threshold set through
the parameter P35
Indicator “TEMPERATURE” slowly flashing
Bit 0 of the Parameter P49 = 0
Conditions for its
activation
“ALARM 1” digital input (terminal 01) enabled
Time set through the parameter P40
“ALARM 1” indicator slowly flashing
Bit 1 of the Parameter P49 = 0
Conditions for its
activation
Engine running from the time set through the Parameter P31
Fuel solenoid activated
“ALARM 2” digital input (terminal 02) shorted to ground
Starting from SW version 08.00.22 this value is set by
parameter P.65.
In the old version this time was set through the parameter P40
“ALARM 2” (“AUX ALARM”) indicator slowly flashing