24 User’s Manual
Bit 7 of the Parameter P39 = 0
Conditions for its
activation
Engine running
Shutdown cycle not in progress
Voltage measured at the D+WL input (terminals 39-40) under
the threshold of 8 (or 16) V.
Message “F05” on the display “MULTIFUNCTION”
Conditions for its
activation
Selector on AUTO or TEST
Engine running
Fuel solenoid activated
The generator doesn’t get in operating window (for two
seconds) within the time limit set through the parameter P32
from the engine start.
Message “F08” on the display “MULTIFUNCTION”
Conditions for its
activation
Selector on AUTO or TEST
Engine not running after P10 starting attempts
“OVERCRANK” indicator slowly flashing
Conditions for its
activation
Detected hardware fault on generator voltage measurement.
Message “F50“ on the display “MULTIFUNCTION”