44 User’s Manual
In the standard version, this terminal acquires the high water temperature alarm. In this
version, it acquires the “engine in threshold” status, and so the high water temperature alarm
is disabled.
Only for this version, the board can activate a block (“F40”) when the KG is closed and the
signal on terminal 10 becomes inactive, with a fixed filter delay of 0.5 seconds.
Document: EAAS0015
Revision: 01 or later
Document: EAAS0006
Revision: 01 or later
Document: EAAS0016
Revision: 03 or later
Document: EAAS0022
Revision: 03 or later