Parameter description
U.M.
Value
Parameter description
Value
P. 0116
Mains/Bus nominal voltage
V
400
P. 0481
Load thresholds mode
0
P. 0119
Mains/Bus number of phases
3
P. 0482
Initial delay
5
P. 0201
Mains measures hysteresis
%
2.5
P. 0483
Low power threshold
0.0
P. 0203
Mains low voltage threshold
%
80.0
P. 0484
Low power delay
60
P. 0204
Mains high voltage threshold
%
110.0
P. 0485
High power threshold
0
P. 0205
Mains presence delay
s
30
P. 0486
High power delay
3
P. 0206
Mains fault delay
s
2
ENGINE
P. 0236
Mains low frequency threshold
%
90.0
P. 0700
Engine type
0
P. 0237
Mains high frequency threshold
%
110.0
P. 0703
Control level via Can-Bus
0
P. 0238
Mains voltage unbalance threshold
%
10.0
P. 0709
Action on Can-Bus fault
1
P. 0847
MCB supplied by the Mains?
1
P. 0710
Idle speed
800
P.0126
Mains/Bus sensor usage
0
P. 0110
Pick-up teeth number
0
P.0855
MCB mode
1
P. 0125
Engine nominal power
0
GENSET
P. 0210
Starting pulse duration
5
P. 0102
Generator nominal voltage
V
400
P. 0211
Starting attempts number
3
P. 0101
Generator number of phases
3
P. 0212
Pause between starting attempts
5
P. 0854
GCB mode
1
P. 0213
Stopping pulse duration in excitation
20
P. 0105
Nominal frequency
Hz
50
P. 0214
Stopping cycle duration
20
P. 0202
Generator measures hysteresis
%
2.5
P. 0215
Cooling cycle duration
45
P. 0106
Generator nominal power
kVA
0
P. 0333
Pick-up over speed threshold
120.0
P. 0218
Delay before supply
s
5
P. 0334
Pick-up over speed delay
0.5
P. 0219
Contactors swap delay
s
2
P. 0331
Over speed (frequency) threshold
120.0
P. 0301
Minimum voltage threshold
%
75.0
P. 0332
Over speed (frequency) delay
0.5
P. 0302
Minimum voltage delay
s
3
P. 4017
Oil pressure sensor type
0
P. 0303
Maximum voltage threshold
%
112.5
P. 4025
Cooling temperature sensor type
0
P. 0304
Maximum voltage delay
s
3
P. 4033
Fuel level sensor type
0
P. 0305
Minimum frequency threshold
%
90.0
P. 0335
Cooling liquid high temp. threshold
92
P. 0306
Minimum frequency delay
s
5
P. 0336
Cooling liquid high temp. delay
2
P. 0307
Maximum frequency threshold
%
110.0
P. 0337
Cooling liquid max. temp. threshold
110
P. 0308
Maximum frequency delay
s
5
P. 0338
Cooling liquid high temp. delay
2
P. 0309
Maximum current threshold
%
90.0
P. 0339
Low oil pressure threshold
1.5
P. 0310
Maximum current delay
s
10
P. 0340
Low oil pressure delay
2
P. 0311
Short circuit threshold
%
500
P. 0341
Min. oil pressure threshold
1.2
P. 0312
Short circuit delay
s
0.5
P. 0342
Min. oil pressure delay
2
P. 0313
Power reverse threshold
%
10.0
P. 0343
High fuel level threshold
90
P. 0314
Power reverse delay
s
10
P. 0344
High fuel level delay
2
P. 0315
Voltage unbalance threshold
%
2.5
P. 0345
Low fuel level threshold
10
P. 0319
Required phase sequence
0
P. 0346
Low fuel level delay
2
P. 0320
Action on wrong phases sequence
1
P. 0347
Min. fuel level threshold
5
P. 0321
Loss of excitation threshold
kvar
0
P. 0348
Min. fuel level delay
20
P. 0323
Action on max. current/short circuit
8
P. 0349
Delay for belt break
20
P. 0324
50V-51V protections enable
0
P. 0353
Cooling liquid low temp. threshold
10
P. 0350
Maximum power threshold
%
100.0
P. 0354
Cooling liquid low temperature delay
0
P. 0351
Maximum power delay
s
0
P. 0357
Protection for belt break
8
P. 0352
Action on maximum power
1
P. 0400
Fuel pump mode
0
P. 0107
C.T. Primary
A
5
P. 0402
Fuel pump activation threshold
15
P. 0139
C.T. secondary
A
5
P. 0403
Fuel pump deactivation threshold
80
P. 0124
CT connection
0
P. 0405
Fuel pump and electrovalve delay
2.0
P. 0131
Connection for auxiliary current
0
P. 0404
Fuel pump maximum activation time
0
Supply voltage:
8..33Vdc
Operating temperature:
-25°C .. 60°C
Current consumption
1100 mA max
External dimensions:
260(L)x202(H)x79(D)mm
Genset rated frequency:
50/60 Hz
Panel cut-out
240(L)x172(H)mm