DANGER
Risk of ignition or explosion
b
Each connection to the protection earth (PE) on the explosion-proof enclosure
must use at least one wire with a cross-section meeting the requirements of the
table below.
Wire cross-section of outer cable S Minimum wire cross-section of the corre‐
sponding protection earth wire S
P
S ≤ 16 mm
2
S
16 mm
2
< S ≤ 35 mm
2
16 mm
2
S > 35 mm
2
0.5 S
Table 1: Minimum wire cross-section for protection earth (PE)