WIRING
Consult local wiring codes and connect to standard 110/120 VAC, 60 Hz, single phase. For supply connections, use
14 AWG or larger wires suitable for at least 90°C or equivalent with an approved ground. We recommend a
minimum 6 foot length of 1/2” IPS rigid, threaded conduit into the junction box supplied, preferably on its own
dedicated 20 amp circuit (see wiring diagram).