Product documentation 1D 3.8.en Rev. E, 10/13 page 35/42
4.5.3 Electric cause II
Breakdown
Possible cause Remedy precaution
Generator voltage < UN
Uneven load distribution
during parallel operation
Difference of voltage
among individual phases
Overheating
Part of winding is
overheated
Fluctuation of output
Overload Reduce load
Break of outer wires Check outer wires
Short-circuit of stator
winding
Measure winding and insulation
resistance, consult producer and
repair
Overload Reduce load
Uneven load Adjust load
Short-circuit of stator
winding
Measure winding and insulation
resistance, consult producer and
repair
Fluctuation of turning
moment
Check driving machine
Potentiometer of statics is
reset
In generator equipped with statics
module-set potentiometer of
statics according to operational
instructions
Break or short-circuit of lead
from statics current
transformer T to statics
Eliminate short-circuit, in case of a
break check current transformer
Tab. 11 Electric causes II