This setting must be set to Enabled so that the RCU will auto-detect and drive the Fusesaver Control
Panel. If this setting is set to disabled the RCU will not power up the Control Panel so no LEDs will
be lit.
7.9.2 Operator Control Panel Ignore Remote Switch
This setting allows Fusesaver Control Panel controls to the Fusesavers such as Trip/Close or change
of protection mode to always be allowed irrespective of the position of the Remote Control ON/OFF
switch. Setting options are:
TRUE: The RCU will allow controls from the panel to be sent to the Fusesaver
irrespective of the position off the Remote Control ON switch.
FALSE: The RCU will disable all controls from the Control Panel if the Remote Control
Switch is ON.
Note that when this setting is TRUE both the Local and Remote Control Source LEDs may be lit
because both sources of control can be enabled.
7.9.3 Always Allow Trip
This setting allows Fusesaver Control Panel TRIP commands to either be passed to the Fusesaver
or rejected by the RCU depending upon the status of the external lever of the Fusesaver. Settings
options are:
TRUE: The RCU will issue the TRIP command to the Fusesaver to trip regardless of
external lever position. The Fusesaver will TRIP regardless of policy file setting for
MANUAL INHIBIT (see Fusesaver Operating Instructions).
FALSE: If the external lever of the Fusesaver is down then the RCU will reject the TRIP
command.
Note; this setting only applies to Fusesaver TRIP commands. Fusesaver CLOSE commands will
always be rejected if the external lever is down regardless of whether the Fusesaver policy for the
external lever is to allow manual operations when the external lever is down.