EasyManua.ls Logo

Siemens 3AH4 - Ambient Conditions; Installation Altitudes

Siemens 3AH4
66 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Description
34 9229 9862 176 0D
2013-08-28
Ambient conditions
Installation altitudes
Insulating capacity The insulating capacity of insulation in air decreases with rising altitude due to the
lower air density. In conformity with IEC 62271-102, the rated lightning impulse
voltage values given in Fig. 43 are valid up to an installation altitude of 1,000 m
above sea level.
At altitudes of 1,000 m and higher, the insulation level must be corrected as shown
in Fig. 45:
3AH4 vacuum circuit-breakers are suitable for use in the
following climate classes in accordance with IEC 60721,
Part 3-3:
Class
Climatic ambient conditions:
3K4
1)
,
3K6
2)
,
3Z2,
3Z5
Biological ambient conditions: 3B1
Mechanical ambient conditions: 3M2
Chemically active substances:
3C2
3)
Mechanically active substances:
3S2
4)
1) Peak value of the 24-hour means: +35 °C
2) Without ice formation and wind-driven precipitation
3) Without occurrence of salt fog and simultaneous condensation
4) Restriction: clean insulating parts
5) Average value, measured over 24 hours
6) Average value, measured over 1 month
Fig. 44 Ambient conditions
U U
0
K
a
U Rated withstand voltage U under standard reference
atmosphere
U
0
Required rated withstand voltage for the installation
location
K
a
Altitude correction factor
K
a
= e
m
(H – 1000)/8150
Calculating the altitude correction factor K
a
:
H = Installation altitude in metres
m = 1 for AC voltage, lightning impulse voltage (between
phases, phase-to-earth, applied longitudinally)
Example
For a required rated withstand voltage of 75 kV at an alti-
tude of 2,500 m, an insulation level of at least 90 kV
under standard reference atmosphere conditions is
required:
90 kV
75 kV e
1
(2500 – 1000)/8150

75 kV 1.2
Fig. 45 Altitude correction factor K
a

Related product manuals