Maintenance
9229 9862 176 0D 53
2013-08-28
Maintenance
Maintenance and servicing
To maintain reliability during the entire operating time and to ensure the operating
cycle numbers, depending on
the type of vacuum circuit-breaker (see “Technical data” on page 33)
the operating conditions see “Ambient conditions” on page 34),
the number of mechanical and electrical operating cycles,
and the operating time,
regular maintenance work must be performed according to the following mainte-
nance plan.
DANGER
High voltage – danger to life
Touching live parts is fatal or causes serious physical injury.
Before beginning maintenance work, note the five safety rules for high-voltage
equipment specified in EN 50110-1, namely:
Isolate from the power supply*)
Secure against reclosing
Verify safe isolation from the power supply
Earth and short-circuit
Cover or cordon off neighbouring live parts
*
)
On the vacuum circuit-breaker, actuate the OPEN, CLOSE and OPEN pushbut-
tons manually one after the other. This ensures that the vacuum circuit-breaker is
open and the closing spring is discharged.
Note
The vacuum circuit-breaker should be taken out of the switch cabinet or switch-
gear for servicing.