Mounting
48 9229 9862 176 0D
2013-08-28
Corresponding to the rated current strength, use M12 screws and nuts – strength
class 8.8 – for connection of the busbars and use the appropriate spring elements
and washers.
When tightening the screws, hold the nuts against tightening torque of 70 Nm with
a suitable screwdriver or socket wrench.
Screw-in depths in the upper and lower terminals
See dimension drawings.