AC current input
I
E
Nominal input current I
EN
min. 1 A, max. 5 A
Input current range I
E
0 to 10 A
Continuous overload capacity
1
12 A
Power consumption per current
path
approx. 0.01VA at I
L
= 1 A
approx. 0.05VA at I
L
= 5 A
approx. 0.1VA at I
L
= 10 A
Surge withstand capability
1
200 A for 1 s
AC voltage input
U
E
Nominal voltage U
EN
max. 500 V ∆
max. 288 V Y
and mono-phase
Power consumption
per line U
L-N
≤0.02 VA at U
E
= 100/√3 V
≤0.33 VA at U
E
= 230 V
Continuous overload capacity
1
U
L-L
= 600 V
Surge withstand capability
1
U
L-L
≤ 850 V / 5 surges 1 s in 5 s
steps
Auxiliary power
Type 1: U
HN
24 V to 60 V DC
Range: U
H
± 20 % of U
HN
Type 2: U
HN
100 to 230 V AC /45-65 Hz
Range: U
H
± 10 % of U
HN
or
U
HN
110 to 250 V DC
U
H
± 20 % of U
HN
Power consumption approx. 3 W, depending on the
output load
1
Continuous and surge overload capacity apply only under reference conditions.