22 SIMEAS E50417-K109U-C322-A1
1.10 Mounting and operation
WARNING!
During operation of electric devices, dangerous voltages are applied
to
certain parts. Ignoring the operator instructions can result in severe injury
or damage. In particular, the safety information must be strictly observed.
The transducer is a build-in device and must therefore be installed in
a distributor box or a control cabinet. After installation, it must be
ensured that all the terminals are properly covered. Only then the
unit is sufficiently protected against accidential touching of live parts.
Installing the device
The location should be largely free from vibrations. The
admissible ambient temperature must be observed (cf.
technical specifications and appendix I).
Running the transducer outside its operating temperature
range can lead to measuring faults and outage of the device.
Screw-type terminals for 2.5 mm
2
or 4 mm
2
max.
The transducer is snapped onto a 35 mm supporting rail
(according to EN 50022). It is suitable for close-to-close
installation. Depending on the power rates (cf. Appendix 1), a
spacing of 20 mm might be required between devices.