1.20 Appendix I
Admissible ambient temperature of the transducer
The admissible maximum ambient temperature of the transducer
depends on the type of mounting and the power loss in the
housing.
The total power loss in the housing is the sum of:
1. the power consumption of the transducer, depending on the
load of the analog outputs and
2. the power loss caused by the measuring signals, usually the
measuring voltage. The power loss caused by the current path
can be neglected for these considerations.
The admissible operating temperature shall be determined using
the following 3 sample diagrams.