EasyManua.ls Logo

Siemens 7KG6000-8EB - Faults and Influence Effects

Siemens 7KG6000-8EB
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14 SIMEAS E50417-K109U-C322-A1
Serial interface
RS 232 C (V.24) optional RS485
For configuration, calibration,
data output
2400 bauds, 8N1
Option RS485
for communication according to
IEC 870-5-103
9600 and 19200 bauds, 8E1
The interface must be operated via a
shielded cable
Binary output
via Optical MOS Relay
Admissible voltage 100 V DC or
100 V AC
Admissible current 120 mA continuous
300 mA for 100 ms
Internal resistance
50
Admissible operating frequency
10 Hz
Faults and influence effects
according to IEC 60688
The relative fault specifications
have the sign ±
Faults under reference conditions related to I
AN
or U
AN
Current, voltage
0.2 % typical
0.5 % max.
Active/reactive/apparent power
0.3 % typical
0.5 % max.
Phase angle
0.5 %
Power factor
1 %
Frequency
absolute 3 mHz
± 0.2 % of the output range

Table of Contents