SITRANS P300 (7MF8.23.. 7MF8.24.. 7MF8.25..)
A5E03434759-01, 08/2011
13
Note
Protect the transmitter from:
Direct heat
Rapid temperature changes
Severe soiling
Mechanical damage
Direct sunlight
NOTICE
The enclosure may only be opened for maintenance, local operation or to make electrical connections.
The installation location is to be as follows:
Easily accessible
As close as possible to the measuring point
Vibration-free
Within the permitted ambient temperature values
Installation configuration
The transmitter can only be used in non-pressurized vessels for level.
Installation height
0(
0$
S
K
R
K
X
Level of non-pressurized vessel
Formula:
Zero point: p
MA =
ρ · g · H
U
Full-scale value: p
ME =
ρ · g · H
O
MA Zero point Δp
MA
Limit point to be adjusted
ME Limit point Δp
ME
Limit point to be adjusted
p Pressure ρ Density of the measured medium in the
container
h
U
Start-of-scale value g Acceleration due to gravity
h
O
Full-scale value
Note
Select the height of the container flange for recording of the transmitter (
measuring point
) such that the lowest level to be
measured is always over the flange or at its upper edge.