$SSHQGL[6-
9

&*&
1216 RMS FORMAT RMS format for inverse time O/C protection
FUNDAMENTAL [ ] Fundamental
TRUE RMS [ ] True rms
1221 MAN.CLOSE Manual close
I>> UNDELAYED [ ] I>> undelayed
I>/Ip UNDELAYED [ ] I>/Ip undelayed
INEFFECTIVE [ ] Ineffective
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
1500 O/C PROT. EARTH
1501 O/C EARTH O/C protection for earth faults
ON []on
OFF [ ] off
1502 IE>> Pick-up value of the high-set stage IE>>
min. 0.05 I/In
max. 25.00 ©©©©
1503 T-IE>> Trip time delay of the high-set stage IE>>
min. 0.00 s
max. 60.00/Ñ ©©©©
1506 MEAS.REPET Measurement repetition
NO []no
YES [ ] yes
1511 CHARACTER. Characteristic of the O/C stage IEp
NORMAL INVERSE [ ] Normal inverse
VERY INVERSE [ ] Very inverse
EXTREMELY INVERS [ ] Extremely inverse
USER CHARACTER. [ ] User characteristics
1512 IE> Pick-up value of the overcurrent stage IE>
min. 0.05 I/In
max. 25.00 ©©©©
1513 T-IE> Trip time delay of the overcurrent stage IE>
min. 0.00 s
max. 60.00/Ñ ©©©©
1514 IEp Pick-up value inverse time O/C stage IEp
min. 0.10 I/In
max. 4.00 ©©©©
1515 T-IEp Trip time delay inverse time O/C stage IEp
min. 0.00 s
max. 10.00/Ñ ©©©©
1516 RMS FORMAT RMS format for inverse time O/C protection
FUNDAMENTAL [ ] Fundamental
TRUE RMS [ ] True rms
1521 MAN.CLOSE Manual close
IE>> UNDELAYED [ ] IE>> undelayed
IE>/IEp UNDELAY. [ ] IE>/IEp undelayed
INEFFECTIVE [ ] Ineffective